Re: help: APC BackUPS 500

From: Ivo Simicevic (qmna@ordersupplies.com)
Date: Sun Jun 11 2000 - 22:31:39 EEST

  • Next message: charlie carroll: "what am I missing here?"

    On Fri, Jun 09, 2000 at 08:19:30PM -0500, Ricardo Denis wrote:
    > hi,
    >
    > i have a APC Back-UPS 500M ups. it did not come with the special serial
    > cable. i wrote them (APC) several times about a wiring diagram so i could
    > at least build my own cable and got no reply at all. i've given up on them
    > and their brand name. does anybody here have wiring diagram of a working
    > cable so i can construct one for my 500M model ups, please? thank you in
    > advance.
    >
    > 73 de rick

    Hi Rick,

    there are lot's of sites on the net with data you need, just use some
    of search engines and you will find it (I did!).

    There are couple of different cables and software so you must be sure
    to match them.
    If it is of any help this is standard connector description :

    Pin Direction Description
    =============================================================
     1 Input RS-232 Shut Down Input (min. 4.5 s high)
     2 Output RS-232 Line Fail Output
     3 Output Normally Open Line Fail Signal
     4 "Output" Common GND
     5 Output Normally Open Low Battery Signal
     6 Output Normally Closed Line Fail Signal
     7
     8
     9 "Output" Chassis GND
    =============================================================

    GL es 73

    Ivo, 9A3TY